Apr 2013
Electricity Distribution
Innovative Protection Solutions
IFI 0510
Live
Apr 2013
Unknown
SP Energy Networks
SP Energy Networks Innovation
Click here to send a question to the contact.
Innovation Funding Incentive
None
LV & 11kV Networks
£150,000.00
At present the interconnected 11kV and 6.6kV networks are protected through the use traditional unit based schemes. However a subset of these networks utilise bidirectional overcurrent and earth fault relays at remote primary substations.

Protection theory shows that it is impossible to achieve true time-based discrimination in a solidly interconnected ring network. In practice, experience shows that suitable grading can be achieved, with limitations (such as the use of relatively high time multipliers, and limited deployment around the ring resulting in large protection zones).

The aim of this project is to investigate and develop a radio-based directional blocking scheme for use on interconnected ring-type 11kV and 6.6kV networks in the SP-M licence area.